1. Product Overview

  • Product Name: Silicone Tubing for Liquid Cooling Systems

  • Product Code: BS-LCS-xx-yy (xx denotes inner diameter, yy denotes outside diameter)

  • Manufacturing Process: High-temperature extrusion molding, platinum-catalyzed vulcanization

  • Key Features: High thermal conductivity, excellent long-term coolant resistance, low extractables, resistance to high/low temperature cycling, flexible and pressure-resistant, electrically insulating.

2. Compliance & Key Requirements

This product is designed to meet the demanding requirements of liquid cooling systems, with emphasis on the following properties:

  • Material Compatibility: Long-term compatibility with common coolants (e.g., deionized water, 50% glycol-water mixture, specialty dielectric fluids) without swelling, cracking, or performance degradation.

  • Low Ionic Extractables: Extremely low leaching of metal ions and impurities to prevent system corrosion and microbial growth.

  • Long-Term Reliability: Ensures extended service life under combined stress from pressure, temperature, and fluid exposure.

  • RoHS & REACH: Compliant with environmental directives.


3. Technical Parameters

Parameter CategorySpecific ParameterUnitSpecification / Requirement
Structure & DimensionsInner Diameter (ID) / Outer Diameter (OD)mmID 6, OD 9(can be customized)
Wall Thicknessmm1.5
Tolerancemm / %±0.15
Fluid PerformanceCompatible Coolant Type(s)-Deionized Water, 50% Glycol-Water Mixture
Burst Pressure (min.)MPa / Bar≥ 0.8
Thermal PerformanceLong-term Operating Temperature Range°C-60°C to +200°C
Thermal ConductivityW/(m·K)1.5
Mechanical PropertiesHardnessShore A80 ±5
Tensile Strength (min.)MPa≥ 4
Elongation at Break%≥ 95

4. Typical Applications

  • Data center server liquid cooling systems

  • Electric vehicle battery pack and powertrain thermal management

  • High-power LED lighting heat dissipation systems

  • Industrial equipment cooling (e.g., lasers, power electronics)

  • High-performance computing (HPC) and gaming device water-cooling loops


5. Recommended Test Standards

  • Dimensions: ASTM D3767

  • Burst Pressure: ASTM D1599

  • Tensile Properties: ASTM D412

  • Hardness: ASTM D2240

  • Heat Aging: ASTM D573

  • Fluid Compatibility: ASTM D471 (with specified coolant and temperature)

  • Ionic Extractables Test: ICP-MS or equivalent method